1、Abstract:Due to the weak support capacity of the power generation equipment at the transmission end of the DC transmission system with a high proportion of renewable energy,the renewable energy power generation equipment faces the risk of over-voltage off grid after the DC fault occurs.In order to p
2、revent the off grid accident of renewable energy,this paper first establishes the simulation model of renewable energy DC transmission system and analyzes the formation mechanism of transient overvoltage at the generator end of renewable energy.Secondly,according to the law of reactive power transmi
3、ssion,this paper analyzes the influence of conventional units,dimmers,electrical distance and other factors on renewable energy off grid,and quantitatively analyzes the voltage regulation sensitivity of conventional units.On this basis,the off grid situation of renewable energy is quantitatively ana
4、lyzed by using the short-circuit ratio index of renewable energy.Finally,according to the analysis results,this paper puts forward some strategies to prevent renewable energy off grid after DC fault,such as improving the short-circuit capacity and improving the high-voltage crossing capacity of the
5、fan,which are verified by a BPA simulation example of a planned DC transmission system.Keywords:DC transmission system;transient overvoltage;dimmer;conventional unit;short circuit ratio;suppression strategy摘 要:含高比例新能源的直流外送系统由于送端发电设备支撑能力薄弱,在直流故障发生后新能源发电设备面临着过电压脱网风险。为了防止新能源脱网事故的发生,首先建立新能源直流外送系统仿真模型分析新
6、能源机端暂态过电压形成机理,其次根据无功传输规律分析常规机组、调相机、电气距离等因素对新能源脱网的影响,定量分析常规机组的电压调节灵敏度,在此基础上利用新能源短路比指标对新能源脱网情况进行量化分析,最后根据分析结果提出了提高短路容量、提高风机高压穿越能力等预防直流故障后新能源脱网的策略,采用某规划的直流外送系统BPA仿真算例验证策略的有效性。关键词:直流外送系统;暂态过电压;调相机;常规机组;短路比;抑制策略0 引言中国的新能源装机总量已位列世界第一,然而新能源发电装置多配置于西部、北部地区,这种集中发直流故障引发直流外送系统新能源脱网问题研究曹昊1*,严欢2,王雷3,宋云亭4,袁性忠2,田浩
7、5(1.华北电力大学(保定),河北省 保定市 071003;2.国网陕西省电力有限公司经济技术研究院,陕西省 西安市 710065;3中国电力工程顾问集团西北电力设计院有限公司,陕西省 西安市 710032;4中国电力科学研究院有限公司,北京市 海淀区 100192;5北京汇思慧能科技有限公司,北京市 海淀区 100080)Research on Renewable Energy Off-grid of DC Transmission System Caused by DC FaultCAO Hao1*,YAN Huan2,WANG Lei3,SONG Yunting4,YUAN Xingzh
8、ong2,TIAN Hao5(1.North China Electric Power Universit(Baoding),Baoding 071003,Hebei Province,China;2.State Grid Shaanxi Electric Power Economic&Technology Research Institute,Xian 710065,Shaanxi Province,China;3.Northwest Electric Power Design Institute Co.,Ltd.of CPECC,Xian 710032,Shaanxi Province,C
9、hina;4.China Electric Power Research Institute,Haidian District,Beijing 100192,China;5.Beijing Huisihuinen Technology Co.,Ltd.,Haidian District,Beijing 100080,China)基金项目:国网陕西省电力有限公司科技项目(陕北特高压直流接入后陕西主网运行特性分析研究,HQ-2021-P-TS-054)。Science and Technology Foundation of State Grid Shaanxi Electric Power Co
10、mpany(Analysis and Research on the Operation Characteristics of Shaanxi Main Network after the UHVDC Access in Northern Shaanxi,HQ-2021-P-TS-054).全球能源互联网Journal of Global Energy Interconnection第 6 卷 第 1 期2023 年 1 月Vol.6 No.1Jan.2023文章编号:2096-5125(2023)01-0071-09 中图分类号:TM715 文献标志码:ADOI:10.19705/ki.is
11、sn2096-5125.2023.01.00872 全球能源互联网 第 6 卷 第 1 期电并远距离传输的特点给电力系统的稳定和能源的利用效率带来了挑战1-2。为实现电能的远距离高质量传输,通常采用高压直流输电技术3。但随着长距离直流输电规模不断增长,“强直弱交”网架特征明显,直流故障后风机进入高电压穿越连锁脱网制约着风能大规模外送4-5。目前的研究表明,大规模新能源直流外送系统的暂态过电压水平与故障类型、直流控制参数、无功补偿类型等因素有关。目前关于无功补偿配置的研究主要集中在不同无功补偿装置性能的比较和无功补偿配置方案两个方面6-10。文献7将非线性系统的数学分析方法引入电力系统,利用非线
12、性因子确定静止无功补偿器(static var compensator,SVC)的配置地点。文献8定义了多馈入直流间的交互影响的权重系数,通过确定无功补偿的边界确定无功最佳补偿地点。文献9比较了新一代调相机和SVC等基于电力电子技术的无功补偿装置,发现调相机具有暂态电压调节能力与动态无功支撑能力。调相机相比SVC等非旋转设备,其无延时的无功调节能力对暂态电压的抑制更具优势11-15。近年来中国已经在部分风电、光伏集中的特高压直流工程送端系统加装调相机,如扎鲁特换流站、湘潭调相机工程、湖南韶山换流站等16。目前工程中主要将大容量调相机配置在换流站高压侧。然而,换流站近区的新能源通常通过分步升压的
13、方式汇集于母线,线路长度较长。这就导致换流站处的调相机难以有效调节直流故障后由新能源产生的盈余无功,然而目前对于小容量分布式调相机的研究尚不完善。此外,大规模新能源直流外送系统中新能源、常规能源和直流之间相互约束。常规机组能够提升系统的短路容量并提供无功支撑,通过增设常规机组能够支撑更多新能源机组接入并提高直流输送功率,有利于新能源的消纳。针对上述问题,本文首先分析经典直流故障引起暂态过电压的机理以及影响新能源机组脱网的关键因素。接着,本文基于PSD-BPA仿真系统构建直流小系统模型,分析常规机组、调相机等无功调节设备对直流故障下的暂态过电压的调控作用,并根据近区风机的脱网情况量化了保障系统稳
14、定运行的短路比指标,随后根据电力系统无功传输的规律分析了新能源场站与换流站间电气距离对短路比指标的影响。最后,本文提出抑制直流故障后新能源脱网的策略,并在规划的某直流系统中验证部分策略的有效性。1 新能源直流外送系统及模型1.1 新能源直流外送系统根据某实际大规模新能源直流外送场景,本文构建了图1所示的直流外送小系统模型,其中送端换流站的直流额定电压为800 kV,A、B、C为换流站近区的三个的新能源场站750 kV并网点,三个站点与换流站间电气距离均不相同。三个站点的风机并网容量均为1950 MW,与新能源变电站相连。配套新能源电站经过升压后,汇集于换流站近区750 kV变电站。C站A站B站
15、换流站受端20 km40 km10 km图 1 小系统仿真模型Fig.1 Small system simulation model1.2 控制系统模型经典控制环节参数见表1,直流控制系统使用的是PSD-BPA仿真软件中的DA数据卡,包括最大触发角控制、直流移相时间等数据;双馈风机使用的是GE数据卡,包括无功测量环节等数据。表 1 典型控制环节参数Table 1 Typical control link parameters控制环节参数项参数值直流控制最大触发角控制增益0.15最大触发角控制时间常数0.012熄弧角参考值19.5直流移相时间/s0.15定电压控制比例增益25定电压控制积分时间常
16、数0.005换相失败预测增益0.055换相失败预测输出角度时间常数0.02风机无功控制无功测量环节时间常数0.02无功外环比例环节放大倍数18无功外环比例积分放大倍数5Vol.6 No.1 曹昊,等:直流故障引发直流外送系统新能源脱网问题研究 732 直流故障引发的暂态过电压问题为便于理论分析,可将风火打捆新能源直流外送系统进行等值简化17。简化后的直流外送等值系统如图2所示。Qbw1QscSCQbs1Qbw2QcPw+jQwPs+jQsPd+jQdPgw+jQgwUwUdUsjxwjxsQbs2图 2 直流外送等值系统Fig.2 DC outgoing equivalent system其中
17、:Pgw、Qgw为风机有功和无功出力;Pw、Qw为风机侧送出有功和无功功率;Ps、Qs为系统侧受入有功和无功功率;Qbw1、Qbw2为风机侧充电无功;Qbs1、Qbs2为系统侧充电无功;Qc为换流站并联补偿无功;Qsc为调相机补偿无功;Uw、Us、Ud分别为风机侧、系统侧和换流站母线电压;xw、xs为风机侧和系统侧电抗。风电送出的有功和无功可由潮流参数得出:gwwPP=(1)lw1bwscgwwQQQQQ-+=(2)dgwsPPP-=(3)ls1bsdc2bwlw1bwscgwsQQQQQQQQQQ-+-+-+=(4)w2d2w2wlwxUQPQ+=(5)s2s2s2slsxUQPQ+=(6)
18、式中:Qlw、Qls为风机侧和系统侧损耗的无功功率。当直流故障如换相失败故障发生后,系统侧、风机侧与换流站间电压关系矢量图如图3所示。其中,Pw、Qw为故障后风机侧送出功率,Ps、Qs为故障后系统侧受入功率。Us Us Usxs Us Ud Psxs(a)换流站和系统侧电压关系Ud Ud Uwxw Ud Uw Pwxw(b)换流站和风机侧电压关系图 3 电压矢量关系图Fig.3 Voltage vector diagram由图3可见,故障后风机侧电压Uw和换流站电压Ud可以通过系统侧电压Us及故障后系统侧受入功率Ps、Qs求得:(7)()wdwqscUxUEQ-=lslwdscgwssQQQQ
19、QQQ-+=(8)dgwssPPPP-+=(9)2sss2ssssd+=UxPUxQUU(10)lwscgwwwQQQQQ-+=(11)gwwwPPP+=(12)2dww2dwwdw+=UxPUxQUU(13)式中:Qsc为故障后调相机无功出力变化;Eq为调相机暂态内电势;xd为调相机暂态内电抗;Qgw为故障后风机无功出力变化;Qlw、Qls为故障后风机侧和系统侧消耗无功变化;Qgw为故障后风机有功出力变化;Pd、Qd为故障后直流有功和无功功率变化。当系统发生直流闭锁或换相失败故障时,直流传输功率中断或大幅跌落,可以认为直流故障后的直流有功、无功传输功率近似为0,故障后直流有功和无功功率变化为
20、:ddd0PPP-=-=(14)ddd0QQQ-=-=(15)风机进入低压穿越期间,控制系统的规律为:风机电压下降越大风机发出的无功就越多,风机发出的有功会被限制在某一较小值。故障后风机发出的有功功率和无功功率为:0gwwtwgw)9.0(QUQ-=(16)gw0gwwgwPPkP-=(17)74 全球能源互联网 第 6 卷 第 1 期式中:Uwt为低穿期间风机机端电压;w为低穿期间风机无功出力比例系数(典型值为12);kw为低穿期间风机有功出力比例系数(典型值为0.10.5);Pgw0、Qgw0为风机额定有功出力、无功出力18。无功功率在电气距离较长时传输困难,一般认为风机和系统侧输送的有功
21、远高于无功。在计算故障后风机侧和系统侧损耗的无功变化量时可进行简化,忽略无功部分Qw、Qs的影响,即 w2d2w2wlwxUPPQ-=(18)s2s2s2slsxUPPQ-=(19)根据上述公式,考虑暂态过程中风机送出的无功变化与线路阻抗消耗的无功变化量,可求得故障后换流站侧和风机侧暂态电压幅值。3 影响新能源脱网的关键因素分析3.1 常规机组开机对暂态过电压的影响本节分析常规机组的开机水平与配置方式对直流故障后系统暂态过电压的影响。以接入图1中A站的风电场为代表校核直流换相失败引起的风电机组机端暂态电压升高量。保持系统的直流输送功率及风电同时率、换流母线与交流系统交换无功、换流母线初始电压不
22、变,在不同开机方式下,计算无调相机接入时直流换相失败后风场的暂态过电压,其中单台常规机组的额定容量为100 MW,计算结果如表2所示。表 2 近区常规开机方式对风电暂态过电压的影响Table 2 Influence of startup mode of near area thermal power on transient overvoltage of wind powerA站开机/台B站开机/台C站开机/台机端暂态 电压升/pu数据编号1000.36811300.34121030.33932000.33043000.31754000.30965000.3017从表2可以看出,A站、B站、C
23、站的常规机组开机都能抑制A站的风电机端暂态过电压。但比较第2、3、4组数据可知,相较于近区的B站或C站增设3台常规机组,A站仅增加1台常规机组开机对暂态电压的抑制效果更好。这说明新能源场站的配套常规机组比近区机组的灵敏度更高。比较第1、4、5、6、7组数据可知,随着A站常规机组开机水平的增加,风电机端的暂态过电压逐渐降低,但是即使将常规机组开机增加到5台,A站风电机端电压依然超过1.3 pu,风机仍然面临着脱网风险。表3为随着A站常规机组数量的增加,近区风电机端暂态过电压降低百分比。数据表明,伴随新能源并网点常规机组开机水平的提高,单台常规机组对风电机端暂态电压的抑制效果逐渐变弱。仅通过增加常
24、规机组开机水平抑制暂态过电压的优势并不突出。这是因为,虽然系统的短路容量伴随常规机组开机水平增加而增大。然而整体而言单台机组对短路容量的增长率的贡献逐渐下降,这意味着单台机组对系统强度的增加也越来越不明显。所以暂态电压降低百分比逐渐下降。表 3 A站典型风电机端暂态过电压降低百分比Table 3 Reduction percentage of transient overvoltage at typical wind turbine terminal of station A新能源场站常规机组开机水平暂态电压降低百分比/%风机1风机2风机3A站1台增至2台1.041.061.022台增至3台0
25、.630.630.643台增至4台0.200.190.20为了进一步分析常规机组开机台数和暂态过电压间的联系,现对二者进行定量的灵敏度分析。定义Uimax为随常规机组开机水平增加新能源机端暂态电压峰值变化量。max1maxmax+-=iiiUUU(20)式中:i为常规机组开机台数;Uimax为常规机组开机i台时新能源机暂态电压峰值。Uimax可以有效表征第i+1台常规机组对新能源机端暂态电压响应的灵敏度。从图4中可以看出常规机组前2台开机对新能源机端暂态过电压的抑制效果最好,Uimax达到0.01以上。随着常规机组开机逐渐增加,对暂态过电压的抑制效果在开机5台时趋近于饱和,继续增加常规机组开机
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- 直流 故障 引发 系统 新能源 问题 研究 曹昊
1、咨信平台为文档C2C交易模式,即用户上传的文档直接被用户下载,收益归上传人(含作者)所有;本站仅是提供信息存储空间和展示预览,仅对用户上传内容的表现方式做保护处理,对上载内容不做任何修改或编辑。所展示的作品文档包括内容和图片全部来源于网络用户和作者上传投稿,我们不确定上传用户享有完全著作权,根据《信息网络传播权保护条例》,如果侵犯了您的版权、权益或隐私,请联系我们,核实后会尽快下架及时删除,并可随时和客服了解处理情况,尊重保护知识产权我们共同努力。
2、文档的总页数、文档格式和文档大小以系统显示为准(内容中显示的页数不一定正确),网站客服只以系统显示的页数、文件格式、文档大小作为仲裁依据,平台无法对文档的真实性、完整性、权威性、准确性、专业性及其观点立场做任何保证或承诺,下载前须认真查看,确认无误后再购买,务必慎重购买;若有违法违纪将进行移交司法处理,若涉侵权平台将进行基本处罚并下架。
3、本站所有内容均由用户上传,付费前请自行鉴别,如您付费,意味着您已接受本站规则且自行承担风险,本站不进行额外附加服务,虚拟产品一经售出概不退款(未进行购买下载可退充值款),文档一经付费(服务费)、不意味着购买了该文档的版权,仅供个人/单位学习、研究之用,不得用于商业用途,未经授权,严禁复制、发行、汇编、翻译或者网络传播等,侵权必究。
4、如你看到网页展示的文档有www.zixin.com.cn水印,是因预览和防盗链等技术需要对页面进行转换压缩成图而已,我们并不对上传的文档进行任何编辑或修改,文档下载后都不会有水印标识(原文档上传前个别存留的除外),下载后原文更清晰;试题试卷类文档,如果标题没有明确说明有答案则都视为没有答案,请知晓;PPT和DOC文档可被视为“模板”,允许上传人保留章节、目录结构的情况下删减部份的内容;PDF文档不管是原文档转换或图片扫描而得,本站不作要求视为允许,下载前自行私信或留言给上传者【自信****多点】。
5、本文档所展示的图片、画像、字体、音乐的版权可能需版权方额外授权,请谨慎使用;网站提供的党政主题相关内容(国旗、国徽、党徽--等)目的在于配合国家政策宣传,仅限个人学习分享使用,禁止用于任何广告和商用目的。
6、文档遇到问题,请及时私信或留言给本站上传会员【自信****多点】,需本站解决可联系【 微信客服】、【 QQ客服】,若有其他问题请点击或扫码反馈【 服务填表】;文档侵犯商业秘密、侵犯著作权、侵犯人身权等,请点击“【 版权申诉】”(推荐),意见反馈和侵权处理邮箱:1219186828@qq.com;也可以拔打客服电话:4008-655-100;投诉/维权电话:4009-655-100。